Origin |
China |
Model Number |
XGN36-12 |
Brand Name |
Zhongyan |
XGN36-12( DXG-12) Packaged Type AC Metal Enclosed Switchgear Fixed Type
1 General 1.1 Electric ratings: rated voltage 3.612KV, rated current up to 3150A 1.2 Application: applicable In the system of three phase single busbar for power receive and distribution
1.3 Standards: IEC 60298
2 Type Designation XGN36-12_ _
_ Rated short-circuit making & breaking current
_ Rated current 12 Rated voltage 36 Design No N Indoor G Fixed type X Packaged type
3 Working conditions 3.1 Ambient temperature-254O 3.2 Altitude:≤1000m 3.3 Humidity: daily average≤95 % Monthly average≤90 % 3.4 Earthquake Intensity≤magnitude 8 3.5 Applicable In the places without corrosive and flammable gas
Note: Customized products are available on your requirements
4.Technical Parameters
| Main Techniacal Parameters |
|
|
| No. |
Items |
Unit |
Data |
| 1 |
Rated voltage |
KV |
3.6 7.2 12 |
| 2 |
Rated current |
A |
630 1250 (1600 2000 2500 3150) |
| 3 |
Rated withstands current (peak) |
KA |
40 50 63 80 (100 125) |
| 4 |
Rated short-time withstands current |
KA |
16 20 25 31.5 (40 50) |
| 5 |
Making & breaking times at rated short-circuit current |
Time |
50 |
| 6 |
Mechanical life |
Time |
10000 |
| 7 |
Rated short-circuit continuous time |
S |
4 |
| 8 |
Rated breaking current |
KA |
16 20 25 31.5 (40 50) |
| 9 |
Rated 1 min industrial frequency voltage withstands |
KV |
(Inter-phase, phase to the earth) 42 (Breaking point) 48 |
| Insulation level Thundering withstands voltage |
KV |
(Inter-phase, phase to the earth) 75 (Breaking point) 85 |
| 10 |
Protection degree |
|
IP3X |
| 11 |
Overall dimension (W×D×H) |
mm |
800×1000×2270 (ZN63A matched, recommended) |
| 800×1200×2270 (ZN28 matched) |
| 800×1600×2270 (Over-headed lines income and outlet, ZN63A matched |
| 800×1400×2200 (ZN63 or ZN28 matched, not recommended) |
| 1600A (The dimensions pending for switchgears above 1600A) |
5 Features 5.1 easy but reliable operation 5.2 Space saving thanks to compact design 5.3 Sound Interlocking functions to prevent the circuit breaker from mis-operation, the switch disconnector from making & breaking on-load, the electrified Interval from being entered, the electrified eathing line being connected and the earthling switch made at the earthling status The mechanical Interlocking makes the maintenance and operation easy 5.4 There is view window at the front panel for easy observation of switch disconnector status
5.5 The getting-through tube is used to fix the bus bar which could limit the expansion of accident Influence and ensure the mechanical intensity of bus bar 5.6 A enclosed cable chamber is equipped for easy cable tap Instillation and monitor which is also available for moisture-proofing,etc
6 Ordering information
The following information should be specified.
6.1 Main circuit diagram, busbardiagram for main circuit allocation diagram.
6.2 Secondary circuit diagram and terminals allocation diagram
6.3 Type, specifications and quantity of the components.
6.4 Material, type and quantity of main bus bar.
6.5 Electric equipments list.
6.6 Spanning and height of busbarstructure, if needed
6.7 Customized products are available on your requirements
6.8 Type and quantity of extra accessories and spare parts, if needed
|