Origin |
China |
Model Number |
1 piece |
Brand Name |
Zhongyan |
External Size |
600*1800*2200 |
Protection Level |
IP54 |
Type |
Distribution Box |
NGG1 (GGD) Low-voltage Switchgear, Fixed Type
1 General 1.1 Electric ratings: rated voltage 400V, 50Hz , rated current up to 3150A 1.2 Application: applicable for the power receive, distribution and control of lighting and distribution, equipments, etc 1.3 Standards: IEC60439-1
2 Type Designation
NGGI-_ _
Short-time withstand voltage
Rated current
Design No. Fixed type Enclosed Company code
3.1 Ambient temperature-540, the average temperature within 24h not exceed +35.
3.2 A1titude≤2000m 3.3 Relative humidity: ≤50% when the temperature is + 40 Higher relative humidity for lower temperature e.g 90 at +20 3.4 Applicable In the places without danger of fire and explosion, chemical pollution, corrosive and flammable gas. 3.5 Inclination not exceeds 5°
Note: Customized products are available on your requirements
| 4.1 Main Technical |
|
|
|
|
|
|
|
|
| Type |
Rated voltage(V) |
Rated current(A) |
Rated short-circuit breaking current(KA) |
Rated short-circuit withstand current(1s)(KA) |
Rated peak withstand voltage(KA) |
|
|
A |
1000 |
|
|
|
|
|
|
| NGG1-1000-15 |
400 |
B |
600(630) |
15 |
|
15 |
|
30 |
|
|
|
C |
400 |
|
|
|
|
|
|
|
|
A |
1500(1600) |
|
|
|
|
|
|
| NGG1-1600-30 |
400 |
B |
1000 |
30 |
|
30 |
|
63 |
|
|
|
C |
600 |
|
|
|
|
|
|
|
|
A |
3150 |
|
|
|
|
|
|
| NGG1-3150-50 |
400 |
B |
2500 |
50 |
|
50 |
|
105 |
|
|
|
C |
2000 |
|
|
|
|
|
|
4.2 Auxiliary circuit plan There are two types of auxiliary circuit plan , power supply plan and power plant plan
4.3 Main bus bar single copper busbaradopted when the rated current≤1600A. Double copper busbaradopted when the rated current>1600A. Brushing & anodizing process adopted which is better than traditional zinc-coated process
| 4.3.1 Selection of horizontal bus bar |
|
|
|
|
| Rated current(A) |
|
Specification of copper bus bar(mm) |
|
| 400 |
|
40×4 |
|
|
|
|
| 630 |
|
50×5 |
|
|
|
|
| 1250 |
|
60×10 |
|
|
|
|
| 1600 |
|
80×10 |
|
|
|
|
| 2000 |
|
2×(60×10) |
|
|
|
|
| 2500 |
|
2×(80×10) |
|
|
|
|
| 3150 |
|
2×(100×10) |
|
|
|
|
|
|
|
|
|
|
|
| 4.3.2 Selection of neutral earthing bus bar |
|
|
|
| Cross section of phase conductor (mm2) |
|
Cross section of PE(N) conductor (mm2) |
| 500720 |
|
|
|
40×4 |
|
|
| 1200 |
|
|
|
50×5 |
|
|
| 1200 |
|
|
|
60×10 |
|
|
5 Features
5.1 The accuracy and quality of the switchgear could be ensured as the framework parts and special parts supplied by us. Modular design of the dimensions concerning (E=20mm), which has cut production time and enhanced efficiency.
5.2 The heat dispensation channel at the top and bottom of the switchgear formulate a ventilation loop to dispens the heat.
5.3 Easy for installation and dismantling.
5.4 The switchgear is with perfect earthling protection system.
5.5 The cover of the switchgear could be removed for installation and adjustment of the main bus bar. There are also rings for lifting and delivery of the switchgear.
5.6 The protection degree is IP30. As per your requirements, switchgears with protection degree of IP20IP40 are available.
5.7 Flexible circuit plans are available.
6 Ordering information
The following information should be specified.
6.1 The full type, including main circuit plan and auxiliary circuit plan.
6.2 The diagram of main circuit system allocation
6.3 Inner allocation diagram of the switchgear
6.4 Electric diagram of auxiliary contact
6.5 Name, type, specification and list of adopted components
6.6 Customized products are available on your requirements
Notes: If you need the dimension graph and detail information I will sent out the technical graph for you.
|