KYN28A-12(Z)(NB) Metalclad AC Enclosed Switchgear, Withdrawable Type
1 General
1.1 Electric ratings: rated voltage 3.6-12KV, the rated current up to 3150A , AC50Hz
1.2 Application: applicable In the system of three phase AC single busbar bar, double busbar bar and single busbar bar stand-by pass to receive and distribute the power.
1.3 Standards: IEC60298
2 Type Designation
KYN 28A-12(Z)(NB)
(B) Improvement code
(N) Company code
(Z) VCB
(12) Rated voltage
(28A) Design No.
(N) Indoor type
(Y) Withdrawable type
(K)Metalclad type
3 WorkingConditions
3.1 Ambient temperature-10 40
3.2 Altitude:≤1000m
3.3 Humidity: daily average≤95%, Monthly average≤90 %
3.4 Earthquake intensity≤magnitude 8
3.5 Applicable In the places without corrosive and flammable gas
Note: Customized products are available on your requirements
4 Main Technical Data
| 4 Main Technical Data |
|
|
| No. |
Items |
Unit |
Data |
|
| Matched VCB |
| ZN63A-12(Vs1) |
VD4,VC |
| 1 |
Rated voltage |
KV |
12 |
12 |
| 2 |
1 min power frequency withstands voltage |
KV |
42 |
42 |
| 3 |
Rated thundering withstands voltage |
KV |
75 |
75 |
| 4 |
Rated frequency |
HZ |
50 |
50 |
| 5 |
Rated current |
A |
630 1250 1600 2000 2500 3150 |
|
| 6 |
Rated current of branched bus |
A |
630 1250 1600 2000 2500 3150 |
|
| 7 |
Rated short-time withstands current (RMS) |
KA |
16 20 25 31.5 |
16 20 25 31.5 |
| 8 |
Rated withstands current (peak) |
KA |
40 50 63 80 100 125 |
41 50 63 80 100 125 |
| 9 |
Rated short-circuit continuous time |
S |
4 |
3 |
| 10 |
Protection degree |
|
The enclosure: IP4X. When the chamber door and trolly door opened, the protection degree is IP2X |
| 11 |
Weight |
KG |
700-1200 |
700-1200 |
8 Ordering Information
The following information should be specified.
8.1 Connection diagram and the allocation diagram.
8.2 The secondary connection diagram and the terminals allocation diagram.
8.3 Name, type, specification and list of adopted components
8.4 List of electric equipments
8.5 Material, type and quantity of main bus bar.
8.6 Type and quantity of extra accessories and spare parts, if needed
8.7 Customized products are available on your requirements
Notes: The installation chart and some structure picture is appendix in the company profile column of self-defined column KYN28A-12(Z)(NB) Metalclad AC Enclosed Switchgear, Withdrawable Type, which helpful to know the detail of information for this type of product.