Origin |
China |
Model Number |
1 piece |
Brand Name |
Zhongyan |
Coil Number |
Autotransformer |
Coil Structure |
Toroidal |
Phase |
Three |
Usage |
Power |
Detailed Product Description
35kV and Below Oil-immersed Transformer
SZ9(M)S10(M)S11(M)-1000-31500/35 Three-phase Oil-immersed Transformer With OLTC
1 General These products are completely accorded to the standard of the IEC 60076 2 Application Standards 2.1 IEC 60076-1-1:1993, IEC60076-2:1993 2.2 IEC 60076-3:2000 3 Model and designation
S Z _ - _ - _/_
(_)Voltage class (_)Rated capacity (_)Sealed Construction
(_) Performance level code (91011)
(Z) OLTC (S) Three-phase Oil-immersed transformer
4 Performance features 4.1 A multi-layer cylinder structure is used for all high-voltage windings
to improve the impact distribution of winding 4.2 For the low voltage windings with capacities ranging from 630 KVA to 3150 KVA,
a cylinder type or spiral structure is used to ensure a high mechanical strength, even
ampere-turn distribution and excellent anti-short-circuit performance
4.3 A locating structure is added to the transformer body which can ensure that no
displacement will occur during transportation, meanwhile trunbuckles are added to
fasteners to ensure that fasteners will not be loosened during the long time operation.
With this structure, core hanging is not necessary 4.4 Core type, with cold rolled grain oriented, silicon steel laminations having excellent
magnetic properties, Insulated and clamped to minimize vibration and noise. The oil will be imputed
to the oil tank in the vacuum.
4.5 The surface painted with primer and finishing coat after being degreased, derusted and
phosphorized, can meet the special operation requirements In metallurgic and petrochemical
Industries as well as moist and dirty areas It is charming In appearance and compact In
design, which can reduce the floor area for Installation, the series and perfect, maintenance-free products
| 4 Major technical parameter |
|
|
|
|
|
| SZ9(M)S10(M)S11(M)-1000-31500/35 Three-phase Oil-immersed Transformer With OLTC |
| Rated capacity KVA |
Rated ration and regulation range |
|
No load |
On load |
Impedance Voltage(%) |
No load current(%) |
| HV |
Tapping range |
LV |
Vector group |
lossed |
lossed |
| (KW) |
(KW) |
| 1000 |
|
|
|
|
|
|
1.7 |
13 |
|
1.1 |
| 1250 |
|
|
|
|
0.69 |
|
2 |
15 |
|
1.1 |
| 1600 |
35 |
|
±2×2.5 |
|
|
2.4 |
18 |
4.5 |
1 |
| 2000 |
|
|
|
|
0.4 |
|
2.9 |
20 |
6.5 |
1 |
| 2500 |
|
|
|
Yd11 |
3.3 |
22 |
1 |
| 3150 |
|
|
|
|
|
4 |
26 |
7 |
0.9 |
| 4000 |
|
|
|
|
|
|
4.9 |
30.5 |
0.9 |
| 5000 |
|
±3×2.5 |
10.5 6.3 |
|
5.8 |
35 |
|
0.85 |
| 6300 |
|
|
|
|
|
7 |
39 |
|
0.85 |
| 8000 |
35 38.5 |
|
|
|
|
|
8.9 |
44 |
7.5 |
0.75 |
| 10000 |
|
|
|
|
|
10.5 |
51 |
|
0.75 |
| 12500 |
|
|
|
|
|
12.6 |
60.5 |
|
0.7 |
| 16000 |
|
|
|
|
|
YNd11 |
15.2 |
74 |
|
0.6 |
| 20000 |
|
|
|
|
|
|
20 |
87.5 |
8 |
0.5 |
| 25000 |
|
|
|
|
|
|
23.4 |
104 |
|
0.5 |
| 31500 |
|
|
|
|
|
|
27.5 |
123.1 |
|
0.45 |
| Weight(kg)body |
oil |
gross |
Tran |
Outline dimension (mm) |
Trail distance (mm) |
| L×W×H |
| sport |
| 1930 |
1240 |
4600 |
3650 |
2850×1930×2430 |
1070×1070 |
| 2200 |
1320 |
4950 |
3800 |
2900×1950×2450 |
1070×1070 |
| 2550 |
1400 |
5300 |
3980 |
2950×1980×2490 |
1070×1070 |
| 2775 |
1560 |
5965 |
4925 |
3010×2065×2540 |
1070×1070 |
| 3300 |
1750 |
6950 |
5683 |
3035×2265×2610 |
1070×1070 |
| 3770 |
1970 |
7900 |
6075 |
3160×2095×2640 |
1070×1070 |
| 4520 |
2260 |
9110 |
7090 |
3295×2325×2890 |
1070×1070 |
| 5480 |
2475 |
10855 |
8465 |
3350×2520×3000 |
1070×1475 |
| 6810 |
2620 |
12300 |
9870 |
3475×2645×3050 |
1070×1475 |
| 8066 |
3330 |
15300 |
12550 |
4900×3126×3277 |
1475×1475 |
| 9705 |
3750 |
17858 |
14700 |
5044×3152×3397 |
1475×1475 |
| 10960 |
4215 |
20042 |
17334 |
5054×3192×3432 |
1475×1475 |
| 13950 |
4900 |
24150 |
21000 |
4900×3800×3680 |
1475×1475 |
| 16700 |
6120 |
30100 |
25200 |
4950×3810×3690 |
1475×1475 |
| 19800 |
8500 |
36500 |
28700 |
5050×3900×3850 |
1475×1475 |
| 263000 |
99650 |
46800 |
39800 |
5130×4050×3920 |
2040×1475 |
|